Equipment Physical Design Standards ATT-TP-76200, Issue 19
AT&T Services, Inc. June 2014
2) Reporting
ATT-TP-76200 Form ESP-001/002 (page 2) shall be used to report:
a. Nominal Heat – Typical operating conditions with AT&T card/traffic load
b. Maximum Heat – This is typically the heat associated with the equipment at
maximum power draw.
E. ATIS Table 1 – Heat Dissipation Data Reporting – Level 3 Reviews / All
Equipment Types
1) General
In addition to the ESP form, ATIS Table 1 Heat Dissipation Summary in Watts
shall be submitted. The table is found in the Alliance for Telecommunications
Industry Solutions: ATIS- 0600010.03.2011 Heat Dissipation Requirements for
Network Telecommunications Equipment).
The document may be downloaded for a fee from the ATIS website
http://www.ATIS.org
. The document is copyright protected so it is not included in
this standard. Refer to the ATIS site for information on access and downloading
of ATIS tables. The ATIS document provides specific information and examples
on how to complete each table.
The intent of Table 1 is to provide heat dissipation at different operating points
from 0% (sleep mode), to Idle (no traffic estimated 25%) up to 100% maximum
for the equipment. It is expected that the 50% (nominal) and the estimated 75%
(full load) entries will provide critical information for cooling system planning
purposes. The 50% (nominal) operating point will typically be the same figure
provided on the ESP form nominal (Total). The 100% (maximum) operating point
will typically be the same figure provided on the ESP form maximum (Total).
Copyright ©2014, AT&T . All Rights Reserved.