POWER AND GROUNDING
Figure 15 depicts a typical power and grounding layout for colocated PPN and EPN cabinets. A
ground wire from the ground block on the EPN cabinet connects to the single-point ground block
on the PPN cabinet. A 6-AWG ground wire connects the single-point ground block on the PPN
cabinet to an approved ground. (Also see ‘‘Grounding,’’ later in this section).
Note that the AC powering for a multi-carrier cabinet is as shown in Figure 15 for the PPN
cabinet.
.
.
.
10 FEET
60-HZ 50-AMP
SERVICE
CONDUCTOR
USE APPROVED GROUND LOCATED NEAREST THE
115-VOLT
OR
208-VOLT
60-HZ 30-AMP
PROVIDED
POWER
PANEL
OR EQUIVALENT
TELEPHONE COMPANY OWNED PROTECTOR GROUND BLOCK
AT THE BUILDING ENTRANCE FACILITY
CUSTOMER
UNIT
REAR
.
.
.
10 FEET
POWER
UNIT
REAR
CORD
NOTE:
POWER CORD
COUPLED
BONDING
10 AWG
RECEPTACLE,
60-HZ 50-AMP
SERVICE
115-VOLT
OR
208-VOLT
60-HZ 30-AMP
NEMA 5-50
OR
L6-30R
6 AWG
10 AWG
COUPLED
BONDING
CONDUCTOR
6 AWG
10 AWG
DISTRIBUTION
GROUND BLOCK
SINGLE-POINT
POWER
TO APPROVED
FRONT
POWER
DISTRIBUTION
FRONT
6 AWG
GROUND BLOCK
NETWORK CABINET
PROCESSOR PORT
NETWORK CABINET
EXPANSION PORT
TO AUXILIARY
CABINET
GROUND
(SEE NOTE)
FIGURE 15. Typical Multi-Carrier System AC Power and Grounding (EPN Colocated)
116